Technical
Data Specification
Manufacturer : UNINDO
Design Standart : SPLN/IEC '76/NFC Under Licence Alstom
Transformer Type : Oil immersed, Hermetically Sealed tottaly Oil filled
Nominal Rating : 2000 KVA
Number of phase : 3
Nominal frequency : 50 Hz
Nominal primary voltage : 20 KV
Nominal secondary voltage : 400 V
Vector group according to IEC '76 : Dyn5
Voltage insulation primary windings : 24 KV
Impulse Voltage : 125 KV
Applied voltage test : 50 KV
Temperature insulation class : A
Ambient temperature : 40 °C
Temperature rise : - Windings : 65 °C
- Oil : 60 °C
Type of Cooling : ONAN
Type of oil : Mineral oil according to IEC 296 Class 1
Esso Univolt - 80
Description of primary tapping : ±2,5 %, ±5 %
Impedance voltage : 7 %
Noise level : 62 dB
Iron losses : 3,600 Watt
Cooper losses : 21,000 Watt
Efficiency :
Load |
4/4 |
3/4 |
2/4 |
¼ |
pf.
0,8 |
98,49 |
98,73 |
98,91 |
98,79 |
pf.
1,0 |
98,78 |
98,98 |
99,12 |
99,03 |
Voltage drop at nominal load : - pf. 0,8 : 5,11 %
- pf. 1,0 : 1,29 %
Weight - Total : 4,365 kg
- Oil : 1,040 kg
Painting Colour : Light Grey RAL 7032
Accessories : Name Plate, rating plate, off load tap changer, filling plug,
Earthing terminal, lifting lugs, Draining Valve,
Bidirectional rollers, H.V. Porcelains bushing.
Optional Accessories : DMCR Protection transformer.
Elastimold Bushing
50 mm2